Description:

Stranded hard drawn copper phase conductor, SLPE insulated, Polyethylene insulated neutral with bare earth conductors.  Polyethylene sheathed cable. Nylon ripcord laid under sheath.

Application:

Aerial SNE Cable is used for house connections.  This cable can only be used for single phase supply.  Cable is made to be suspended in the air.  Aerial SNE Cable is also suitable for underground general use.  Split concentric cable suitable for power distribution as an underground or overhead cable.

Specifications:

  • SPLIT NEUTRAL AND EARTH
  • SANS 1507-6
  • CONDUCTOR TYPE: Insulated neutral and bare earth conductors

Available Sheath Colours:

  • Black

Download PDF
CABLE SIZE
mm²
10 16
 Phase Conductor Resistance (0hm/Km) DC @20ºC  1.89 1.2
Phase Conductor Impedance (0hm/km)  2.34  1.5
 Phase Conductor Strand size (mm) & No.  1.35 x 7  1.74 x 7
 Phase Conductor Insulation Thickness (mm)  0.7  0.7
 Phase conductor 0D (mm)  5.45  6.4
 Neutral Size (mm²)  10  16.0
 Neutral conductor Strand size (mm) & No.  1.33 x 7  1.67 x 7
Earth size (mm²)  7.5  11.0
Earth Conductor Strand Size (mm) & No.  1.78 x 3  2.2 x 3
 Communication Cores – Solid – OD (mm) & No  0.8 x 2  0.8 x 2
Current Rating (A)  67  89.0
 (In air 30ºC ambient -max Conductor Temperature 90ºC)
Nominal Sheath Thickness (mm)  1.4  1.6
 Approximate Cable OD (mm)  12  14.0
Approximate Cable Mass (Kg/Km)  319  488.0