Description:

Two Systems are available.

Self Supporting System: Consists of four cores of hard drawn stranded compacted aluminium conductors of the same cross-sectional area insulated with Carbon loaded XLPE and laid up around a bare aluminium alloy supporting core.

Supporting Core System: Consists of three phase cores of hard drawn stranded compacted aluminium conductors of the same cross-sectional area insulated wirth carbon loaded XLPE and laid up around a bare aluminium alloy supporting core.

Application:

ABC Cable is used in place of bare conductor overhead distribution systems.  I provides a higher level of safety and reliability and economy with reduced maintenance and operative costs and reduced risks of vandalism and theft.  It is ideal for difficult terrains and urban areas and is a flexible system that is easier to reroute thatn the conventional overhead line methods.

Specifications:

Available Sheath Colours:

  • Black

Download PDF
TECHNICAL INFORMATION (SELF SUPPORTING SYSTEM)
DESCRIPTION NORMAL CONDUCTOR DIAMETER NORMINAL CORE DIAMETER CONDUCTOR RESISTANCE @20°C CONDUCTOR RESISTANCE @80°C CURRENT RATING SHORT CIRCUIT RATING NORMINAL BUNDLE DIAMETER MAXIMUM DESIGN LOAD APPROX. BUNDLE WEIGHT
 (mm) (mm)  (Ω/km) (Ω/km) (A) (kA) (mm) (kN) (kg/km)
35 x 4 7.2 10.4 0.868 1.078 144 3.2 25.1 7 566.38
 50 x 4  8.37  11.57  0.641  0.796  283  4.6  27.9  9  733.08
 70 x 4  9.95  13.55  0.443  0.55  228  6.4  32.7  14  979.99
TECHNICAL INFORMATION (SUPPORTING CORE SYSTEM)
DESCRIPTION NORMAL CONDUCTOR DIAMETER NORMINAL CORE DIAMETER CONDUCTOR RESISTANCE @20°C CONDUCTOR RESISTANCE @80°C CURRENT RATING SHORT CIRCUIT RATING NORMINAL BUNDLE DIAMETER MAXIMUM DESIGN LOAD APPROX. BUNDLE WEIGHT
 35 x 3 + 54.6 7.2 10.4 0.868 1.078 144 3.2 25.1 6 574.86
 50 x 3 + 54.6  8.37  11.57  0.641  0.796  183  4.6  27.9  6  701.07
 70 x 3 + 54.6  9.95  13.55  0.443  0.550  228  6.4  32.7  6  878.21